Chiller Plant Manager
live
Status
RUN
commanded auto
Power draw
26.2 kW
rated 40 HP (29.8 kW)
Run hours
33,480
lifetime
Health
84 /100
runtime + vibration composite
Energy meter
EM_19
OK
Power draw — 30 dkW · daily mean while running
Range
2425.627.228.830.412 Jun27 Jun11 Julrated 29.8 kW
Slow upward creep in specific power usually means impeller wear or a throttled discharge valve — flagged automatically at +10% vs the 90-day floor.
Live readings1 min sampling
Run statusRUN
Motor current41.9 A
Speed2,950 rpm (DOL)
Est. flow≈ 272 m³/h
Winding temp72 °C
Vibration (manual log)TRENDING UP
kWh yesterday (EM_19)535.65
Health
Maintenance & nameplatefrom CMMS
Duty groupCondenser
Rated power40 HP (29.8 kW)
StarterDOL · auto rotation with standby
Run hours33,480
Greasing dueevery 2,000 h · next in 520 h
Alignment checkDUE — vibration trending
Mech. sealNo leakage reported
tap anywhere to keep screen awake