Reports this month
42
0 failed deliveries
Savings MTD
₹ 41,800
vs normalized baseline
Savings YTD
₹ 5.1 L
-6.2% vs baseline
Baseline model R²
0.93
CV(RMSE) 8.4 %
Daily plant report — 10 Jul 2026delivered 07:00 · PDF + WhatsApp
Report date
| Segment | kWh | Share | Note |
|---|---|---|---|
| Chillers (EM_06/08/12) | 12,279 | 55% | EM_08 estimated |
| Primary CHW pumps | 466 | 2.1% | |
| Condenser pumps | 1,147 | 5.1% | EM_21/24 estimated |
| Cooling tower fans | 532 | 2.4% | |
| Secondary / zone pumps | 800 | 3.6% | |
| Non-plant HVAC + building | 7,095 | 31.8% | |
| Total facility | 22,319 | 100% |
| Cooling delivered | 10,577 ton-hrs |
| Plant efficiency (day avg) | 1.10 kW/TR |
| Electricity cost | ₹ 1.8 L |
| Make-up water | 94.9 kL |
Measured savings vs baselineMWh / month · IPMVP Option C
Baseline model: kWh = 6.91 × CDD_wb + 0.42 × occupied_rooms + 3,120 — fit on Jul 2024 – Jun 2025, R² 0.93, CV(RMSE) 8.4 %. Months where actual exceeded baseline (early monsoon 2025) are shown as zero savings, not netted away.
Scheduled reportson-demand runs are audited
| Report | Cadence | Recipients | Format | Last on-demand run | |
|---|---|---|---|---|---|
| Daily plant report | Daily 07:00 | Chief engineer, shift WhatsApp group | — | ||
| Weekly efficiency review | Mon 08:00 | Chief engineer, GM | — | ||
| Monthly energy & cost | 1st 09:00 | Energy manager, Finance | PDF + XLSX | — | |
| M&V savings statement | Monthly | Corporate sustainability | — | ||
| Meter health exceptions | Daily 07:00 | O&M vendor | — |