Chiller Plant Manager
live
Plant kW/TR now
1.10
target 0.85
Best chiller
CH-1
0.90 kW/TR @ 78% load
Worst chiller
CH-3
1.50 kW/TR · +76% vs comm.
ΔT 24 h avg
4.5 °C
design 6.0
Ton-hours today
9,840
vs 10,740 yesterday
Sequencing score
71 /100
4 wrong-stage days this week
Range
Plant efficiency — 7 dkW/TR
0.70.911.21.317:0005:0015:00target 0.85
Header ΔT — 7 d°C
01.83.55.3717:0005:0015:00design 6.0
Chiller scoreboard — live vs commissioningclick a row → asset detail
ChillerStatusLoadkWkW/TRCOPΔT evapCond. approachvs commissioningRun hrsStarts
CH-1 375 TRRUN78%2630.904.04.6 °C1.6 °C+10%41,2105,321
CH-2 130 TROFF30,4804,102
CH-3 265 TRRUN71%2821.502.44.4 °C4.8 °C+76%44,8906,018
Part-load efficiency curveskW/TR vs % load · measured 90 d
CH-1CH-2CH-3Commissioning ref
0.711.41.72.130%70%100%
CH-3 sits 70–80% above its commissioning curve across the whole load range — consistent with condenser fouling (finding F-2607), not a control issue.
Chillers — running status todayhourly · today, fixed
CH-1
CH-2
CH-3
RunOffTrip
06:00 trip on CH-3 auto-reset in 18 min. CH-2 (130 TR) covered the 11:00–16:00 lunch peak; the CH-1 + CH-2 combination beats CH-3 at today's load — staging-order review is queued as finding F-2555.
Cooling delivered — 7 dton-hours / day
05k9k14k5 Jul6 Jul7 Jul8 Jul9 Jul10 Jul11 Jul