Analyze

Plant performance

all KPIs server-computed · one definition everywhere
Plant kW/TR now
1.10
target 0.85
Best chiller
CH-4
0.68 kW/TR @ 70% load
Worst chiller
CH-3
1.50 kW/TR · +76% vs comm.
ΔT 24 h avg
4.5 °C
design 6.0
Ton-hours today
9,840
vs 10,740 yesterday
Sequencing score
71 /100
4 wrong-stage days this week
Range
Plant efficiency — 7 dkW/TR
0.70.911.21.317:0005:0015:00target 0.85
Header ΔT — 7 d°C
01.83.55.3717:0005:0015:00design 6.0
Chiller scoreboard — live vs commissioningclick a row → asset detail
ChillerStatusLoadkWkW/TRCOPΔT evapCond. approachvs commissioningRun hrsStarts
CH-1 300 TRRUN78%2110.904.04.6 °C1.6 °C+10%41,2105,321
CH-2 300 TROFF39,4805,102
CH-3 300 TRRUN71%3201.502.44.4 °C4.8 °C+76%44,8906,018
CH-4 500 TROFF22,1402,874
Part-load efficiency curveskW/TR vs % load · measured 90 d
CH-1CH-2CH-3CH-4Commissioning ref
0.50.91.31.72.130%70%100%
CH-3 sits 70–80% above its commissioning curve across the whole load range — consistent with condenser fouling (finding F-2607), not a control issue.
Chillers — running status todayhourly · today, fixed
CH-1
CH-2
CH-3
CH-4
RunOffTrip
06:00 trip on CH-3 auto-reset in 18 min. CH-2 covered the 11:00–16:00 lunch peak; CH-4 (most efficient) unused for 21 days — staging-order review is queued as finding F-2555.
Cooling delivered — 7 dton-hours / day
05k9k14k5 Jul6 Jul7 Jul8 Jul9 Jul10 Jul11 Jul