Status
RUN
78% load
kW/TR
0.90
commissioning 0.82
COP
4.0
Cond. approach
1.6 °C
baseline 1.5
Run hours
41,210
5,321 starts
Next service
2026-08-14
last 2026-05-14
Condenser approach — 30 d°C · daily median at run
Range
Live readings30 s sampling
| CHW supply / return | 9.4 °C / 14 °C |
| Evap approach | 0.8 °C |
| CDW in / out | 33.4 °C / 38.1 °C |
| Input power | 263 kW |
| Energy meter | EM_06 — OK |
| Trip status | NORMAL |
Open findings on this asset
None — asset clean.
Part-load curve — measured vs commissioningkW/TR vs % load
Measured 90 dCommissioning
Maintenance & nameplatefrom CMMS
| Type | Screw, water-cooled |
| Capacity | 375 TR |
| Refrigerant | R-134a |
| Commissioned | 2013 |
| Commissioning kW/TR | 0.82 |
| Last service | 2026-05-14 |
| Next service | 2026-08-14 |
| Open work orders | None |