Chiller Plant Manager
live
Status
OFF
available
kW/TR
commissioning 0.84
COP
Cond. approach
°C
baseline 1.5
Run hours
30,480
4,102 starts
Next service
2026-09-02
last 2026-06-02
Condenser approach — 30 d°C · daily median at run
Range
11.21.31.41.612 Jun27 Jun11 Julcommissioning 1.5
Live readings30 s sampling
CHW supply / return— (off)
Evap approach
CDW in / out
Input power0 kW
Energy meterEM_08 — DEAD, panel-kW fallback
Trip statusNORMAL
Open findings on this asset
None — asset clean.
Part-load curve — measured vs commissioningkW/TR vs % load
Measured 90 dCommissioning
0.80.91.11.21.430%70%100%MeasuredCommissioning
Maintenance & nameplatefrom CMMS
TypeScrew, water-cooled
Capacity130 TR
RefrigerantR-134a
Commissioned2016
Commissioning kW/TR0.84
Last service2026-06-02
Next service2026-09-02
Open work ordersNone