Assets / Cooling tower
CT-1 — induced-draft cell
Status
RUN
mode Auto
Fan power
8.4 kW
Approach
3.8 °C
target ≤ 4.0 vs wet-bulb
Run hours
30,140
fan, lifetime
Health
87 /100
Approach temperature — 30 d°C · daily median vs wet-bulb
Range
Live readings1 min sampling
| Fan status | RUN |
| Fan command | Auto |
| CDW entering / leaving | 38.4 °C / 33.3 °C |
| Ambient wet-bulb | 29.1 °C |
| Basin temperature | 32.8 °C |
| Basin level | NORMAL |
| Vibration switch | HEALTHY |
Open findings on this asset
None — asset clean.
Maintenancefrom CMMS
| Type | Induced draft, counterflow · FRP casing |
| Fan | 4-blade axial · 8.4 kW motor |
| Fill inspection | OK, last quarter |
| Nozzle / distribution check | OK |
| Blowdown / water treatment | Conductivity-controlled · last dosed today 06:00 |
| Drift eliminators | Intact (visual, monthly) |