Assets / Cooling tower

CT-2 — induced-draft cell

fan mode Auto · health 85/100
Status
RUN
mode Auto
Fan power
8.1 kW
Approach
4.1 °C
target ≤ 4.0 vs wet-bulb
Run hours
29,760
fan, lifetime
Health
85 /100
Approach temperature — 30 d°C · daily median vs wet-bulb
Range
2.93.23.53.84.112 Jun27 Jun11 Jultarget 4.0
Approach drifting up at equal wet-bulb — possible fill scaling or nozzle blockage. Finding F-2588 open, ≈ ₹ 900/day penalty across running chillers.
Live readings1 min sampling
Fan statusRUN
Fan commandAuto
CDW entering / leaving38.4 °C / 33.3 °C
Ambient wet-bulb29.1 °C
Basin temperature32.8 °C
Basin levelNORMAL
Vibration switchHEALTHY
Open findings on this asset
F-2588 · CT-2 approach drifting up₹ 0.9k/day
Maintenancefrom CMMS
TypeInduced draft, counterflow · FRP casing
Fan4-blade axial · 8.1 kW motor
Fill inspectionDUE — approach drifting (F-2588)
Nozzle / distribution checkScheduled with fill inspection
Blowdown / water treatmentConductivity-controlled · last dosed today 06:00
Drift eliminatorsIntact (visual, monthly)