Status
RUN
mode Auto
Fan power
16.4 kW
Approach
4.1 °C
target ≤ 4.0 vs wet-bulb
Run hours
29,760
fan, lifetime
Health
85 /100
Approach temperature — 30 d°C · daily median vs wet-bulb
Range
Approach drifting up at equal wet-bulb — possible fill scaling or nozzle blockage. Finding F-2588 open, ≈ ₹ 900/day penalty across running chillers.
Live readings1 min sampling
| Fan status | RUN |
| Fan command | Auto |
| CDW entering / leaving | 38.4 °C / 33.3 °C |
| Ambient wet-bulb | 29.1 °C |
| Basin temperature | 32.8 °C |
| Basin level | NORMAL |
| Vibration switch | HEALTHY |
Open findings on this asset
F-2588 · CT-2 approach drifting upMaintenancefrom CMMS
| Type | Induced draft, counterflow · FRP casing |
| Fans | 4 × axial · 16.4 kW total |
| Fill inspection | DUE — approach drifting (F-2588) |
| Nozzle / distribution check | Scheduled with fill inspection |
| Blowdown / water treatment | Conductivity-controlled · last dosed today 06:00 |
| Drift eliminators | Intact (visual, monthly) |