Status
OFF
mode Auto
Fan power
0.0 kW
Approach
— °C
target ≤ 4.0 vs wet-bulb
Run hours
28,410
fan, lifetime
Health
90 /100
Approach temperature — 30 d°C · daily median vs wet-bulb
Range
Live readings1 min sampling
| Fan status | OFF |
| Fan command | Auto |
| CDW entering / leaving | — (isolated) |
| Ambient wet-bulb | 29.1 °C |
| Basin temperature | — |
| Basin level | — |
| Vibration switch | HEALTHY |
Open findings on this asset
None — asset clean.
Maintenancefrom CMMS
| Type | Induced draft, counterflow · FRP casing |
| Fans | 1 × axial · 5.5 kW total |
| Fill inspection | OK, last quarter |
| Nozzle / distribution check | OK |
| Blowdown / water treatment | Conductivity-controlled · last dosed today 06:00 |
| Drift eliminators | Intact (visual, monthly) |