Chiller Plant Manager
live
Status
RUN
commanded auto
Power draw
6.4 kW
rated 10 HP (7.5 kW)
Run hours
30,110
lifetime
Health
90 /100
runtime + vibration composite
Energy meter
EM_26
OK
Power draw — 30 dkW · daily mean while running
Range
5.86.36.87.27.712 Jun27 Jun11 Julrated 7.5 kW
Slow upward creep in specific power usually means impeller wear or a throttled discharge valve — flagged automatically at +10% vs the 90-day floor.
Live readings1 min sampling
Run statusRUN
Motor current10.2 A
Speed2,950 rpm (DOL)
Est. flow≈ 68 m³/h
Winding temp72 °C
Vibration (manual log)NORMAL
kWh yesterday (EM_26)178.87
Health
Maintenance & nameplatefrom CMMS
Duty groupPrimary CHW
Rated power10 HP (7.5 kW)
StarterDOL · auto rotation with standby
Run hours30,110
Greasing dueevery 2,000 h · next in 1,890 h
Alignment checkOK (last quarter)
Mech. sealNo leakage reported
tap anywhere to keep screen awake