Chiller Plant Manager
live
Status
OFF
standby, available
Power draw
0.0 kW
rated 10 HP (7.5 kW)
Run hours
29,840
lifetime
Health
92 /100
runtime + vibration composite
Energy meter
EM_25
OK
Power draw — 30 dkW · daily mean while running
Range
5.66.16.77.27.712 Jun27 Jun11 Julrated 7.5 kW
Slow upward creep in specific power usually means impeller wear or a throttled discharge valve — flagged automatically at +10% vs the 90-day floor.
Live readings1 min sampling
Run statusOFF
Motor current0 A
Speed
Est. flow
Winding tempambient
Vibration (manual log)NORMAL
kWh yesterday (EM_25)61.97
Health
Maintenance & nameplatefrom CMMS
Duty groupPrimary CHW
Rated power10 HP (7.5 kW)
StarterDOL · auto rotation with standby
Run hours29,840
Greasing dueevery 2,000 h · next in 160 h
Alignment checkOK (last quarter)
Mech. sealNo leakage reported