Chiller Plant Manager
live
Status
RUN
commanded auto
Power draw
24.8 kW
rated 40 HP (29.8 kW)
Run hours
22,110
lifetime
Health
87 /100
runtime + vibration composite
Energy meter
panel kW
no dedicated meter
Power draw — 30 dkW · daily mean while running
Range
22.524.526.628.630.612 Jun27 Jun11 Julrated 29.8 kW
Slow upward creep in specific power usually means impeller wear or a throttled discharge valve — flagged automatically at +10% vs the 90-day floor.
Live readings1 min sampling
Run statusRUN
Motor current39.7 A
Speed2,950 rpm (DOL)
Est. flow≈ 272 m³/h
Winding temp72 °C
Vibration (manual log)NORMAL
Health
Maintenance & nameplatefrom CMMS
Duty groupGuest Floor 40 HP
Rated power40 HP (29.8 kW)
StarterDOL · auto rotation with standby
Run hours22,110
Greasing dueevery 2,000 h · next in 1,890 h
Alignment checkOK (last quarter)
Mech. sealNo leakage reported